10

Design Maximum Load

A design maximum heating condition might be -25C outdoors with a 20C indoor temperature. Losses from our condo from conduction through the walls (subscript w) and windows (subscript f for fenestration) would be

\begin{align}

q_c = \sum{\frac{A}{R}(T_i-T_o)} &= \left(\frac{A_w}{R_w} +\frac{A_f}{R_f}\right)(T_i-T_o)\\

&= \left(\frac{36.5}{2.5} + \frac{11.5}{0.6}\right)\left(20-(-25)\right)\\

&= 1520\;\rm  W

\end{align}

and we would also need to supply enough energy to warm up the air that leaks in to replace the air that leaks out. We will be close using constant values for specific heat $C_p = 1004\;\rm J/kgK$, density $\rho = 1.2\;\rm kg/m^3$ and dimensions from our condo model above that results in $0.032\;\rm m^3/s$ air flow for 0.5 air changes per hour.

\begin{align}

q_i = \dot m C_p (T_i-T_o) &= \rho \dot V C_p(T_i-T_o)\\

&= 1.2\times 0.032\times 1004\times (20-(-25)) \\

&= 1735\;\rm W

\end{align}

for a total of 3255 W  or 3.3 kW (or 11000 Btu/hr for comparison to product literature) heating power required on a cold dark night in mid-winter and we would need heating equipment that could deliver that output.

If we needed this level of heating 24/7 for the entire month of January it would amount to about 2400 kWh of heating power. Fortunately this is a worst case and our overall electric consumption in January is about half that amount, which makes sense given average temperatures just below freezing. For performance prediction we will need to look at more than just the most demanding case when the temperatures are coldest. We have ignored humidity in our estimates and could need more energy to humidify for comfort. Humidity will be much more important for air conditioning situations.

Heating Equipment

Electric resistance heaters like baseboards or electric fan heaters are simple, cheap, and transfer 100% of the electrical energy into the room air.

Mini-Split Heat Pumps like the Fujitsu Halcyon line are a common energy efficient solution for heating small and medium sized living spaces. There are DC versions like this one from HotSpot Energy, however they don’t have a DC unit that can handle a Canadian winter. The advantage of heat pumps over traditional electric resistance heating is higher output. Heat pumps provide more heat than the electrical energy that goes into them. They transfer heat from a cold location to a warmer location through a refrigeration cycle and have an apparent efficiency of more than 100%, which just sounds wrong, so we call it a Coefficient of Performance (COP).

A heat pump system will be more effective if it can draw heat from a reservoir that is warmer than the outside air, like ground water or lake water.

https://www.ontario.ca/page/earth-energy-systems-ontario provides more detail.

Fired Heaters like furnaces or stoves can burn fossil fuels like propane or bio-fuels like wood. They are simple, moderately priced, and transfer up to about 85% of the heating energy value of the fuel to the room air.

Heat Pump Figures of Merit

The dimensionless coefficient of performance is the ratio of the thermal energy transferred to or from the living space to the electrical input energy. The COP varies depending on the heat pump design, the refrigerant, and the temperatures at either end of the cycle. The COP varies from a low of around 2 when heating a living space from low outdoor air source temperatures ($-20^\circ\rm C$) to a practical high of about 4.5 in standard air conditioning applications.

The Seasonal energy efficiency ratio (SEER) is an averaged measure for performance over the entire air conditioning season in BTU/Wh to agree with units in common use the USA. A dimensionless value for comparison with COP can be obtained by dividing SEER/3.412, as there are 3.412 BTU per Wh.

The Heating seasonal performance factor (HSPF) is an averaged measure for performance over the entire heating season in BTU/Wh like the SEER.

Both HSPF and SEER will be better than the limiting COP values would suggest, as much of both the heating and air conditioning seasons involve low differences between indoor and outdoor temperatures, where the performance of heat pumps improves. For comparing different heat pumps, higher values of HSPF, SEER, and COP all represent better performance.

Additional Heat Generation

People inside a living space give off heat. How much heat will depend on the people (age, size, gender, etc.) and their activity level.

Any device that consumes electricity inside the living space either stores it as potential energy as in a battery, or gives off the equivalent amount of energy as heat. For example, the energy consumed operating a refrigerator is ultimately transferred to the room air as heat, while a lot of the energy stored in a hot water heater ultimately goes down the drain.

Sunlight shining in through the windows will warm the interior, providing solar heat gain.

None of these additional sources should be considered in your maximum heat load design calculations, but they will become important in predicting the actual heating required under normal operations.

License

Icon for the Creative Commons Attribution 4.0 International License

APSC 100 Tiny House Project Copyright © 2019 by Rick Sellens is licensed under a Creative Commons Attribution 4.0 International License, except where otherwise noted.

Share This Book